Buderus RC35 Operations Instructions Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
System settings (Service menu – Settings)
Logamatic EMS RC35 programming unit - Subject to technical modifications
34
6
Room setback mode: The heating system operates as if in setback mode (as described under
“reduced operation”), if the room temperature falls below the selected night temperature (set
value). Boiler and heating circuit pump stop (as described under setback mode “shut-down
mode”) if the room temperature exceeds the set night temperature by more than 1 K.
This setback mode is only possible if a programming unit/remote control is installed in a
representative room (reference room) or if the room temperature is captured by an external room
temperature sensor.
Outdoor setback mode: The heating system operates as in reduced heating mode (as
described under setback mode “reduced operation”) if the adjusted outside temperature does
not reach the value of an adjustable outside temperature threshold. The heating system remains
off above this threshold (as described under setback mode “shut-down mode”). This setback
mode is suitable for heating circuits which do not have their own programming unit / remote
control unit. The operating mode protects the rooms from cooling down too much once a certain
outside temperature is reached.
6.3.5 Frost protection
The frost protection function offers the following options:
no frost protection (frost protection is switched off).
outside temp. (outside temperature sensor required) The heating circuit pump starts
automatically if the outside temperature falls below the adjustable frost protection temperature
threshold.
room temperature (room temperature sensor of the RC35 or RC2x) The heating circuit pump
starts automatically if the room temperature falls below the permanently set value of 5 °C. The
heating circuit pump stops automatically if the room temperature rises above 7 °C.
At what outside temp. should reduction be interrupted?
EN 12831 requires that, for the maintenance of a level of comfortable heat, heating areas and heat
sources be designed to deliver a specific output if the heating system cools down to a specific value
through night setback.
CAUTION: System damage due to frost!
The settings no frost protection and room temperature provide either no frost
protection or inadequate frost protection. When these settings are selected, the display
shows a message indicating the risk of freezing.
B For reliable frost protection, use the outside temp. setting.
The setting room temperature offers no absolute frost protection, as lines routed
through external walls may freeze up, for example, although the temperature in the
reference room may be significantly above 5 °C.
Page view 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 59 60

Comments to this Manuals

No comments