Logamatic EMS RC35 programming unit - Subject to technical modifications
19
Commissioning
5
5.2 Checklist: important parameters for commissioning
When commissioning the device, ensure the satisfaction of both parties, making sure that the
heating system meets the customer's needs and will not give cause for complaints. In our
experience, the following parameters are very important for the satisfaction of the system user:
B Find out the system owner's requirements and preferences regarding:
Setting options
Factory
setting
SERVICE
MENU\
settings\
The required type of reduction
(night setback)
Outdoor setback
mode;
reduced operation;
Room setback mode;
shut-down mode
Outdoor
setback
mode
heating circuit x,
page 28
The required control mode outside temp. contr.,
room temp. controlled
outside
temp. contr.
heating circuit x,
page 31
The correct heating curve By means of the
following parameters:
design temperature,
minimum outside
temperature, offset,
and set room
temperature
heating circuit x,
page 28
The correct building type
(adjusting the outside temp.)
light, medium, heavy medium plant data,
page 24
The switching frequency of the
DHW circulation pump
1)
1) This function is not available for boilers with UBA1.x, DBA, UBA-H3 or for DHW heating according to the
instantaneous water heating principle.
permanent operation,
1 x, 2 x, 3 x, 4 x, 5 x,
6 x per hour for
3 minutes at a time
2 x domestic hot
water, page 37
Priority DHW yes, no yes heating circuit x,
page 29
Switching program
(times)
Standard program
(e.g. family), user
defined program
family heating circuit x,
page 30
Tab. 7 Checklist: important parameters for commissioning