Page 1 - Logamatic EMS

For contractorsRead carefully before installation and servicing.Installation and service instructionsRoom controllerLogamatic EMS6 720 618 477-00.1RS

Page 2 - Contents

InstallationLogamatic EMS RC35 programming unit - Subject to technical modifications103 3 Installation3.1 Choosing the right installation position3.1.

Page 3

Logamatic EMS RC35 programming unit - Subject to technical modifications11Installation3 3.1.2 Installation on boilerInstallation directly on the boile

Page 4 - Guide to instructions

InstallationLogamatic EMS RC35 programming unit - Subject to technical modifications123 3.3 Installation and connectionsThe wall mounting base can be

Page 5 - 1.1 Key to symbols

Logamatic EMS RC35 programming unit - Subject to technical modifications13Installation3 B A jumper is required at terminals “EXT” [6] (delivered condi

Page 6 - 1.2 Safety instructions

Principles of operationLogamatic EMS RC35 programming unit - Subject to technical modifications144 4 Principles of operation4.1 Overview of controls K

Page 7 - 2 Product information

Logamatic EMS RC35 programming unit - Subject to technical modifications15Principles of operation4 4.2 Introduction to the service menuYou can use the

Page 8 - 2.4 Specification

Principles of operationLogamatic EMS RC35 programming unit - Subject to technical modifications164 4. The SERVICE\SETTINGS menu opens.Turn rotary sele

Page 9 - 2.6 Accessories

Logamatic EMS RC35 programming unit - Subject to technical modifications17Principles of operation4 4.3 Overview of the service menuThe SERVICE MENU is

Page 10 - 3 Installation

CommissioningLogamatic EMS RC35 programming unit - Subject to technical modifications185 5 Commissioning5.1 General commissioningOperation Result1. Sw

Page 11 - 3.2 Types of installation

Logamatic EMS RC35 programming unit - Subject to technical modifications19Commissioning5 5.2 Checklist: important parameters for commissioningWhen com

Page 12 - 6 720 618 477-03.1RS

ContentsLogamatic EMS RC35 programming unit - Subject to technical modifications2 ContentsGuide to instructions . . . . . . . . . . . . . . . . . . .

Page 13 - Installation

CommissioningLogamatic EMS RC35 programming unit - Subject to technical modifications205 5.3 Quick commissioning (menu quick operation)B Press to open

Page 14 - 4 Principles of operation

Logamatic EMS RC35 programming unit - Subject to technical modifications21Commissioning5 5.4 Detailed commissioningB Check whether the factory setting

Page 15 - Principles of operation

CommissioningLogamatic EMS RC35 programming unit - Subject to technical modifications225 5.6 Shutting down/switching offThe RC35 programming unit is p

Page 16

Logamatic EMS RC35 programming unit - Subject to technical modifications23System settings (Service menu – Settings)6 6 System settings (Service menu –

Page 17

System settings (Service menu – Settings)Logamatic EMS RC35 programming unit - Subject to technical modifications246 6.1.1 Building type (adjusting th

Page 18 - 01.01.2000

Logamatic EMS RC35 programming unit - Subject to technical modifications25System settings (Service menu – Settings)6 Example:Fig. 6 This greatly simpl

Page 19 - Commissioning

System settings (Service menu – Settings)Logamatic EMS RC35 programming unit - Subject to technical modifications266 6.2 Boiler dataB Turn rotary sele

Page 20

Logamatic EMS RC35 programming unit - Subject to technical modifications27System settings (Service menu – Settings)6 6.3 Heating circuit data This cha

Page 21 - 5.5 System handover

System settings (Service menu – Settings)Logamatic EMS RC35 programming unit - Subject to technical modifications286 Heating curvestd. tmp. ( – 10 °C)

Page 22 - 5.7 Operating information

Logamatic EMS RC35 programming unit - Subject to technical modifications29System settings (Service menu – Settings)6 What outside temp. should be used

Page 23 - 6.1 Plant data

Logamatic EMS RC35 programming unit - Subject to technical modifications3Contents 6 System settings (Service menu – Settings) . . . . . . . . . . . .

Page 24

System settings (Service menu – Settings)Logamatic EMS RC35 programming unit - Subject to technical modifications306 What is the desired maximum flow

Page 25 - 1 Current outside temperature

Logamatic EMS RC35 programming unit - Subject to technical modifications31System settings (Service menu – Settings)6 6.3.1 Assignment of programming u

Page 26 - 6.2 Boiler data

System settings (Service menu – Settings)Logamatic EMS RC35 programming unit - Subject to technical modifications326 6.3.3 Heating curveParameters: de

Page 27 - 6.3 Heating circuit data

Logamatic EMS RC35 programming unit - Subject to technical modifications33System settings (Service menu – Settings)6 Fig. 7 Setting the heating curve.

Page 28

System settings (Service menu – Settings)Logamatic EMS RC35 programming unit - Subject to technical modifications346 • Room setback mode: The heating

Page 29

Logamatic EMS RC35 programming unit - Subject to technical modifications35System settings (Service menu – Settings)6 In parameter At what outside temp

Page 30

System settings (Service menu – Settings)Logamatic EMS RC35 programming unit - Subject to technical modifications366 6.4 DHWB Turn rotary selector a

Page 31

Logamatic EMS RC35 programming unit - Subject to technical modifications37System settings (Service menu – Settings)6 DHW circulation2)3)Is a circulati

Page 32

System settings (Service menu – Settings)Logamatic EMS RC35 programming unit - Subject to technical modifications386 Should the LED of the single char

Page 33 - 6 720 618 477-06.1RS

Logamatic EMS RC35 programming unit - Subject to technical modifications39System settings (Service menu – Settings)6 6.5 Solar dataB Turn rotary selec

Page 34

Guide to instructionsLogamatic EMS RC35 programming unit - Subject to technical modifications4 Guide to instructionsThese installation and service ins

Page 35 - 5°C -15°C

System settings (Service menu – Settings)Logamatic EMS RC35 programming unit - Subject to technical modifications406 6.6 RC35 calibrationB Turn rotary

Page 36 - SERVICE\SETTINGS

Logamatic EMS RC35 programming unit - Subject to technical modifications41System settings (Service menu – Settings)6 6.7 Contact detailsContact detail

Page 37

DiagnosisLogamatic EMS RC35 programming unit - Subject to technical modifications427 7 DiagnosisThe diagnosis service menu contains a number of tools

Page 38

Logamatic EMS RC35 programming unit - Subject to technical modifications43Diagnosis7 7.2 Monitor value You can use the monitor value menu to view the

Page 39 - 6.5 Solar data

DiagnosisLogamatic EMS RC35 programming unit - Subject to technical modifications447 7.3 Error messageYou can use the error message menu to view the m

Page 40 - 6.6 RC35 calibration

Logamatic EMS RC35 programming unit - Subject to technical modifications45Diagnosis7 7.4 Heating curveWith the htg. charact. curve you can graphically

Page 41 - 6.7 Contact details

ServiceLogamatic EMS RC35 programming unit - Subject to technical modifications468 8 ServiceWith the servicing menu (not possible on boilers with UBA1

Page 42 - 7 Diagnosis

Logamatic EMS RC35 programming unit - Subject to technical modifications47Reset9 9 ResetThe RESET menu allows you to reset• all parameters to their fa

Page 43 - 7.2 Monitor value

TroubleshootingLogamatic EMS RC35 programming unit - Subject to technical modifications4810 10 TroubleshootingThis fault table lists possible system f

Page 44 - 7.3 Error message

Logamatic EMS RC35 programming unit - Subject to technical modifications49Troubleshooting10 A01 810 DHW stays cold.The system continuously tries to he

Page 45 - 7.5 Versions

Logamatic EMS RC35 programming unit - Subject to technical modifications5Key to symbols and safety instructions1 1 Key to symbols and safety instructi

Page 46 - 8 Service

TroubleshootingLogamatic EMS RC35 programming unit - Subject to technical modifications5010 A01 815 Low loss header sensor faulty.This may result in t

Page 47

Logamatic EMS RC35 programming unit - Subject to technical modifications51Troubleshooting10 A11 804 internal error Heating system is in emergency mode

Page 48 - 10 Troubleshooting

TroubleshootingLogamatic EMS RC35 programming unit - Subject to technical modifications5210 A18 825 Two master operating units in system.RC35 and RC2x

Page 49 - Troubleshooting

Logamatic EMS RC35 programming unit - Subject to technical modifications53Troubleshooting10 A2x 829 RC20/RF as remote control.RC20/RF unable to transm

Page 50

TroubleshootingLogamatic EMS RC35 programming unit - Subject to technical modifications5410 A3x 807 HCx flow sensor is defect.The heating circuit pump

Page 51

Logamatic EMS RC35 programming unit - Subject to technical modifications55Service menu RC3511 11 Service menu RC35SERVICE MENUquick operationsettingsd

Page 52

Index Logamatic EMS RC35 programming unit - Subject to technical modifications56IndexAAccessories . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 53

Logamatic EMS RC35 programming unit - Subject to technical modifications57Index PPlant data, Service menu – Settings. . . . . . . 23Power failure . .

Page 54

Logamatic EMS RC35 programming unit - Subject to technical modifications58 Notes

Page 55 - 11 Service menu RC35

Logamatic EMS RC35 programming unit - Subject to technical modifications59 Notes

Page 56

Key to symbols and safety instructionsLogamatic EMS RC35 programming unit - Subject to technical modifications61 1.2 Safety instructionsInstallation a

Page 57

BuderusCotswold Way, Warndon, Worcester WR4 9SWCustomer service: 0844 892 3004Technical support: 0844 892 4224Fax: 01905 753130www.buderus-commercial

Page 58

Logamatic EMS RC35 programming unit - Subject to technical modifications7Product information2 2 Product information2.1 Correct useThe RC35 programming

Page 59

Product informationLogamatic EMS RC35 programming unit - Subject to technical modifications82 2.4 SpecificationTemperature sensor characteristicsWhen

Page 60

Logamatic EMS RC35 programming unit - Subject to technical modifications9Product information2 2.5 Validity of these instructions for function modules