Logamatic EMS RC35 programming unit - Subject to technical modifications
29
System settings (Service menu – Settings)
6
What outside temp.
should be used for
reduced operation?
– 20 °C to
+10 °C
5 °C Temperature threshold for outdoor
setback mode (Æ page 33).
Adjustment only if the setback mode
is set to “Outdoor setback mode”.
Frost protection
What temp. should be
used to trigger frost
protection?
outside temp.,
room temperature,
no frost protection
outside
temp.
Room temperature adjustment only if
RC2x or RC35 have been assigned
to the heating circuit (Æ page 34).
Which frost protection
temp. should be used?
– 20 °C to
+10 °C
5 °C Refers to outside temperature
(Æ page 34).
At what outside temp.
should reduction be
interrupted?
OFF,
– 30 °C to
+10 °C
OFF Setback in accordance with
EN 12831 standard (Æ page 34).
Should domestic hot
water priority be
activated?
yes, no no
Mixer
2)
Is a mixer installed? yes, no yes Can only be set for heating circuit 2
onwards.
2)
What running time
does the mixer have?
10 sec. to
600 sec.
120 sec.
2)
What increase should
be used for the boiler?
0K to 20K 5K
2)
Screed drying
2)
Should a drying cycle
be carried out?
yes, no no Adjustment only if floor has been
selected. DHW heating is not
enabled while screed is drying.
2)
Every how many days
should the flow temp.
be raised?
every day, every
2nd day to
every 5th day
every day
2)
By how many Kelvin
should the flow temp.
be raised each time?
0K to 40K 5K
2)
Menu item Input range
Factory
setting Other information
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1